Temperature Measurement Event
This event is generated when the device provides actual per component or sensor temperature readings.
Event Type: PH_DEV_MON_HW_TEMP
Description: Event capturing temperature readings for network devices and environmental monitors
Cisco IOS (SNMP),Cisco Nx-OS (SNMP), Juniper JunOS (SNMP), Juniper SRX JunOS (SNMP), Alcatel AOS
(SNMP),Avaya/Nortel ERS (SNMP), H3C Comware,
Dell EqualLogic (SNMP)
F5 Big-IPOS (SNMP), APC NetBotz (SNMP)
Cisco UCS (UCS API)
Key Attributes: Varies depending on the source – see portions in bold below.
Name | Id | Type | Description |
Event Type | eventType | string | Event type set to PH_DEV_MON_HW_TEMP |
Event Severity | eventSeverity | uint16 | 1 set to INFO |
Event Severity
Category |
eventSeverityCat | string | Set to Low. In general, takes the values Low, Medium and High. Event Severities 0-4 are mapped to Low, 5-8 are mapped to Medium and 9-10 are mapped to High |
Event Receive Time | phRecvTime | Date | Time at which AccelOps generated this event |
Reporting IP | reptDevIpAddr | Date | IP address of device reporting this event. In this case set to the device reporting the utilization (same as Host name attribute) |
Relaying IP | relayDevIpAddr | Date | IP address of device relaying this event from the source to AccelOps. In general it could be a syslog-ng IP address but in this, since AccelOps talks to the device directly, Relaying IP is set to AccelOps IP Address. |
Raw Event Log | rawEventMsg | string | Raw event containing all attributes in comma separated “[Attribute] = value” format. |
Host name | hostName | string | Host name (as in AccelOps CMDB) of the device whose overall hardware health is being reported |
Host IP Address | hostIpAddr | IP | Access IP (as in AccelOps CMDB) of the device whose overall hardware health is being reported |
Hardware
Component Name |
hwComponentName | String | Name of the temperature sensor |
Temperature
(Celsius) |
envTempDegC | uint32 | Temperature in Celsius |
Temperature
(Fahrenheit) |
envTempDegF | uint32 | Temperature in Fahrenheit |
High Temperature
Threshold (Celsius) |
envTempHighThreshDegC | uint32 | High temperature threshold in Celsius (only for Cisco IOS, H3C Comware, Alcatel AOS,APC NetBotz) |
Temp Offset High
(Celsius) |
envTempOffHighDegC | uint32 | Offset from high threshold in Celsius, set to envTempHighThreshDegC – envTempDegC (only fo r Cisco IOS, H3C Comware, Alcatel AOS,APC NetBotz) |
High Temperature
Threshold (Fahrenheit) |
envTempHighThreshDegF | uint32 | High temperature threshold in Fahrenheit (only for Cisco IOS, H3C Comware, Alcatel AOS,APC NetBotz) |
Temp Offset High
(Fahrenheit) |
envTempOffHighDegF | uint32 | Offset from high threshold in Fahrenheit, set to envTempHighThreshDegF – envTempDegF (only for Cisco IOS, H3C Comware, Alcatel AOS,APC NetBotz) |
Env Sensor Id | envSensorId | string | Temperature sensor id (only for APC NetBotz) |
Env Sensor Label | envSensorLabel | string | Temperature sensor label (only for APC NetBotz) |
Env Sensor
Enclosure Id |
envSensorEnclosureId | string | Temperature sensor enclosure id (only for APC NetBotz) |
Humidity Measurement Event
This event is generated when the device provides actual per component or sensor temperature readings.
Event Type: PH_DEV_MON_HW_HUMIDITY
Description: Event specifying relative humidity settings
Source: APC NetBotz (SNMP)
Key Attributes: Varies depending on the source – see portions in bold below.
Name | Id | Type | Description |
Event Type | eventType | string | Event type set to PH_DEV_MON_HW_HUMIDITY |
Event
Severity |
eventSeverity | uint16 | 1 set to INFO |
Event
Severity Category |
eventSeverityCat | string | Set to Low. In general, takes the values Low, Medium and High. Event Severities 0-4 are mapped to Low, 5-8 are mapped to Medium and 9-10 are mapped to High |
Event
Receive Time |
phRecvTime | Date | Time at which AccelOps generated this event |
Reporting IP | reptDevIpAddr | Date | IP address of device reporting this event. In this case set to the device reporting the utilization (same as Host name attribute) |
Relaying IP | relayDevIpAddr | Date | IP address of device relaying this event from the source to AccelOps. In general it could be a syslog-ng IP address but in this, since AccelOps talks to the device directly, Relaying IP is set to AccelOps IP Address. |
Raw Event
Log |
rawEventMsg | string | Raw event containing all attributes in comma separated “[Attribute] = value” format. |
Host name | hostName | string | Host name (as in AccelOps CMDB) of the device whose overall hardware health is being reported |
Host IP
Address |
hostIpAddr | IP | Access IP (as in AccelOps CMDB) of the device whose overall hardware health is being reported |
Env Sensor
Id |
envSensorId | string | Humidity sensor id |
Env Sensor
Label |
envSensorLabel | string | Humidity sensor label |
Env Sensor
Enclosure Id |
envSensorEnclosureId | string | Humidity sensor enclosure id |
Relative
Humidity |
envHumidityRel | uint32 | Relative Humidity |
Airflow Measurement Event
This event is generated when the device provides actual per component or sensor temperature readings.
Event Type: PH_DEV_MON_HW_AIRFLOW
Description: Event specifying relative humidity readings
Source: APC NetBotz (SNMP)
Key Attributes: Varies depending on the source – see portions in bold below.
Name | Id | Type | Description |
Event Type | eventType | string | Event type set to PH_DEV_MON_HW_HUMIDITY |
Event Severity | eventSeverity | uint16 | 1 set to INFO |
Event Severity
Category |
eventSeverityCat | string | Set to Low. In general, takes the values Low, Medium and High. Event Severities 0-4 are mapped to Low, 5-8 are mapped to Medium and 9-10 are mapped to High |
Event Receive
Time |
phRecvTime | Date | Time at which AccelOps generated this event |
Reporting IP | reptDevIpAddr | Date | IP address of device reporting this event. In this case set to the device reporting the utilization (same as Host name attribute) |
Relaying IP | relayDevIpAddr | Date | IP address of device relaying this event from the source to AccelOps. In general it could be a syslog-ng IP address but in this, since AccelOps talks to the device directly, Relaying IP is set to AccelOps IP Address. |
Raw Event
Log |
rawEventMsg | string | Raw event containing all attributes in comma separated “[Attribute] = value” format. |
Host name | hostName | string | Host name (as in AccelOps CMDB) of the device whose overall hardware health is being reported |
Host IP
Address |
hostIpAddr | IP | Access IP (as in AccelOps CMDB) of the device whose overall hardware health is being reported |
Env Sensor Id | envSensorId | string | Humidity sensor id |
Env Sensor
Label |
envSensorLabel | string | Humidity sensor label |
Env Sensor
Enclosure Id |
envSensorEnclosureId | string | Humidity sensor enclosure id |
Air Flow
(0.1meter/min) |
envAirFlow | uint32 | Air flow in 0.1 meters/minute |
Dew point Measurement Event
This event is generated when the device provides actual per component or sensor temperature readings.
Event Type: PH_DEV_MON_HW_DEWPT
Description: Event specifying relative dew point temperature readings
Source: APC NetBotz (SNMP)
Key Attributes: Varies depending on the source – see portions in bold below.
Name | Id | Type | Description |
Event Type | eventType | string | Event type set to PH_DEV_MON_HW_DEWPT |
Event
Severity |
eventSeverity | uint16 | 1 set to INFO |
Event
Severity Category |
eventSeverityCat | string | Set to Low. In general, takes the values Low, Medium and High. Event Severities 0-4 are mapped to Low, 5-8 are mapped to Medium and 9-10 are mapped to High |
Event
Receive Time |
phRecvTime | Date | Time at which AccelOps generated this event |
Reporting IP | reptDevIpAddr | Date | IP address of device reporting this event. In this case set to the device reporting the utilization (same as Host name attribute) |
Relaying IP | relayDevIpAddr | Date | IP address of device relaying this event from the source to AccelOps. In general it could be a syslog-ng IP address but in this, since AccelOps talks to the device directly, Relaying IP is set to AccelOps IP Address. |
Raw Event
Log |
rawEventMsg | string | Raw event containing all attributes in comma separated “[Attribute] = value” format. |
Host name | hostName | string | Host name (as in AccelOps CMDB) of the device whose overall hardware health is being reported |
Host IP
Address |
hostIpAddr | IP | Access IP (as in AccelOps CMDB) of the device whose overall hardware health is being reported |
Env Sensor Id | envSensorId | string | Humidity sensor id |
Env Sensor
Label |
envSensorLabel | string | Humidity sensor label |
Env Sensor
Enclosure Id |
envSensorEnclosureId | string | Humidity sensor enclosure id |
Temperature
(Celsius) |
envTempDegC | uint32 | Dew point temperature in Celsius |
Temperature
(Fahrenheit) |
envTempDegF | uint32 | Dew point temperature in Fahrenheit |
Audio Level Measurement Event
This event is generated when the device provides actual per component or sensor temperature readings.
Event Type: PH_DEV_MON_HW_AUDIO
Description: Event specifying audio level readings
Source: APC NetBotz (SNMP)
Key Attributes: Varies depending on the source – see portions in bold below.
Name | Id | Type | Description |
Event Type | eventType | string | Event type set to PH_DEV_MON_HW_AUDIO |
Event
Severity |
eventSeverity | uint16 | 1 set to INFO |
Event
Severity Category |
eventSeverityCat | string | Set to Low. In general, takes the values Low, Medium and High. Event Severities 0-4 are mapped to Low, 5-8 are mapped to Medium and 9-10 are mapped to High |
Event
Receive Time |
phRecvTime | Date | Time at which AccelOps generated this event |
Reporting IP | reptDevIpAddr | Date | IP address of device reporting this event. In this case set to the device reporting the utilization (same as Host name attribute) |
Relaying IP | relayDevIpAddr | Date | IP address of device relaying this event from the source to AccelOps. In general it could be a syslog-ng IP address but in this, since AccelOps talks to the device directly, Relaying IP is set to AccelOps IP Address. |
Raw Event
Log |
rawEventMsg | string | Raw event containing all attributes in comma separated “[Attribute] = value” format. |
Host name | hostName | string | Host name (as in AccelOps CMDB) of the device whose overall hardware health is being reported |
Host IP
Address |
hostIpAddr | IP | Access IP (as in AccelOps CMDB) of the device whose overall hardware health is being reported |
Env Sensor
Id |
envSensorId | string | Humidity sensor id |
Env Sensor
Label |
envSensorLabel | string | Humidity sensor label |
Env Sensor
Enclosure Id |
envSensorEnclosureId | string | Humidity sensor enclosure |
Audio Sensor
Level |
envAudioLevel | uint32 | Audio Sensor Level |